Characteristic
Secure circuit for preventing starting when abnormal signal is detected by built-in flame detection.
Safety protection device with built-in ignition failure or sudden extinction in combustion.
The function of burning flammable gas in the combustion chamber before ignition.
Manual (reset) operation function when built-in ignition.
Parameter
Rated voltage: AC200-240V 50*60HZ single-phase
Use ambient temperature: -20 degrees C~60 degrees C
Use ambient humidity: 35%~85%
Output voltage and current: AC250V 5A
Power consumption: MAX 7W, AC30mA below
Main working time
PRE PURGE TIME: 15±4S
POST IGNTION TIME: 6S±2S
Ignition cutoff time: 3S±1S
Extinguish response time: within 1S
Post purge time (ignition loss time) : 20S±5S
Flame detection (Probe mode)
Ignition detection current: DC 2μA or above
Fire detection current: DC less than 0.7μA